Communication between Mitsubishi FX3U PLC and SCADA via RS485BD
Hi Friends, Here i want share with you a tutorial on how to establish Communication between Mitsubishi FX3U PLC and Elipse SCADA via RS485 BD  
 The required Items for the setup is as follows 
 | Sr. no. | Material | 
| 1 | PLC Type : FX Series | 
| 2 | CPU      : FX3U | 
| 3 | Module   : FX3U RS485BD | 
| 4 | SCADA Make : Elipse | 
| 5 | SCADA Type : 20/300/ Unlimited Tags | 
| 6 | Other | 
| Figure Connection between PC(SCADA) & PLC(FX3U) | 
 The required cables are as follows 
 | Sr. no. | Item | Description | 
| 1 | Medoc cable (MITSU-CAB2A) | Prog. cable for FX PLC | 
| 2 | Converter Cables *1 | Comm. Cable for PC ,PLC & Converter | 
 *1 To connect the SCADA to the controller the RS 232 to RS 485 Converter  is used. The Converter is having RS422/485 port for connecting to PLC & RS232 port on other side for connection to PC.
 As the FX-485BD Port is used, PLC parameter settings are required on PLC side.
PLC Parameter Configuration for Channel1:
1. Baud Rate: 9600.
2. Data Bits: 7 bits
3. Parity : Even
4. Stop Bit: 1 bit
5. Sum Check: Yes
6. Transmission Control: Without CR, LF
7. H/W Type: RS485
8. Station No.: 01
PLC Communication Parameter Settings using GX Developer:
 PLC Parameter Configuration for Channel1:
1. Baud Rate: 9600.
2. Data Bits: 7 bits
3. Parity : Even
4. Stop Bit: 1 bit
5. Sum Check: Yes
6. Transmission Control: Without CR, LF
7. H/W Type: RS485
8. Station No.: 01
PLC Communication Parameter Settings using GX Developer:
| PLC Communication Parameter Settings using GX Developer | 
 SCADA Program settings
  SCADA Driver Details:
 | Driver | MELSEC-A.dll | 
| Version | 1.02 | 
| Latest Update | 2004.10.20 | 
| Driver Help | Melsec-A_US.pdf | 
Driver Setting Parameters:
P1: 1 (Comm. Port)
P2: 3721(Comm. Parameters: 9600 bps, 7 data bits, Even
Parity & 1 stop bit)
P3: 300 (Timeout in milliseconds)
P4: 10 (For RS485)
Other needed Configuration is done through “Extra Configuration “Dialog as follows:
 P1: 1 (Comm. Port)
P2: 3721(Comm. Parameters: 9600 bps, 7 data bits, Even
Parity & 1 stop bit)
P3: 300 (Timeout in milliseconds)
P4: 10 (For RS485)
Other needed Configuration is done through “Extra Configuration “Dialog as follows:
• Snap shot of Driver Settings in Elipse SCADA software
 
 Step 1: Enter the Driver Parameters P1-P4.
 | Driver Parameters | 
Step 2: Click on “Extra” button to edit settings.
  Step3: In “Extra” menu select “Protocol” option to edit Protocol  Settings.
 | “Protocol” option | 
 Tag Addressing Parameters:
 
 The Tags are generated by using N1-N4 parameter settings as follows:
 
 N1: Station Number (e.g.: 1)
 N2: CPU Number (normally 255)
 N3: Variable Type (e.g.: 14 for D Register)
 N4: Variable Address (e.g.:10 for D10 Register)
 Scan: User Defined
 
 • Snap shot of Tag Addressing Parameters in Software